    Title: SARS專責醫院負壓病房廢氣排放大氣擴散模式
    Authors: 張正興;鄭光榮
    Contributors: 淡江大學土木工程學系
    Keywords: 計算流體力學;大氣擴散;嚴重急性呼吸道症候群;Computational fluid dynamics (CFD);Atmospheric dispersion;SARS
    Date: 2007-04
    Issue Date: 2014-02-08 19:27:41 (UTC+8)
    Abstract: 2003年嚴重急性呼吸道症候群的爆發,造成了全世界的驚恐,各醫院也在此波疫情過後增建負壓隔離病房,以收治受此新興病毒感染之病患。而醫院附近之居民則因醫院增建負壓病房,且因負壓病房廢氣的排放是否會受到病毒的感染而驚恐及害怕。而本研究則以負壓隔離病房廢氣的排放,利用計算流體力學(CFD)來模擬其排放後濃度分佈,其結果顯示:其距地面1.5及17.5公尺時最大濃度發生於和平醫院之東北方之某政府單位之建築物周圍,距地面35公尺之最大濃度則較不受到建築之影響,而呈現一放射狀之分佈;平均濃度則受到各風向發生機率之影響,其距地面1.5及17.5公尺之最大平均濃度則發生於最頻風向角時。當和平醫院在收治SARS病患時,宜減少地面高濃度區域之人類活動,而高樓層則需注意空調設備之使用,以減少感染SARS病毒之機率。
    Relation: 2007年全球華人風工程論壇論文集=Proceedings of Global Chinese Wind Engineering Forum(GCWEF 2007)